AF16-30-10-14模塊化接觸器1SBL177001R1410來自ABB,上海銳譽為你優(yōu)惠提供。
概要信息
Extended Product Type:
AF16-30-10-14
Product ID:
1SBL177001R1410
Catalog Description:
AF16-30-10-14 250-500V50/60HZ-DC Contactor
Long Description:
AF16 contactors are used for controlling power circuits up to 690 V AC and 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. AF... contactors include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. AF contactors can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. AF contactors have built-in surge protection and do not require additional surge suppressors. The AF... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC or DC operated - Accessories: a wide range of accessories is available.
分類
產(chǎn)品? - 低壓產(chǎn)品及系統(tǒng)
? - 控制產(chǎn)品
? - 接觸器
? - 模塊化接觸器
Ordering
Dimensions
Container Information
Package Level 1 Gross Weight:
Environmental
Ambient Air Temperature:
Close to Contactor for Storage -60...+80 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Maximum Operating Altitude Permissible:
Resistance to Shock acc. to IEC 60068-2-27:
Closed, Shock Direction: B1 25 g
Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
Resistance to Vibrations acc. to IEC 60068-2-6:
5...300 Hz 4 g closed position / 2 g open position
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2008 Q1
Technical
Rated Operational Power AC-3 (Pe):
(220 / 230 / 240V) 4 kW
(380 / 400V) 7.5 kW
(415V) 9 kW
(440V) 9 kW
(500V) 9 kW
(690V) 9 kW
Rated Operational Current AC-1 (Ie):
(690V) 40°C 30 A
(690V) 60°C 30 A
(690V) 70°C 26 A
Number of Main Contacts NO:
Number of Main Contacts NC:
Number of Auxiliary Contacts NO:
Number of Auxiliary Contacts NC:
Rated Control Circuit Voltage (Uc):
50 Hz 250...500 V
60 Hz 250...500 V
DC Operation 250...500 V
1SBL157001R1310 AF12-30-10-13
1SBL157001R1410 AF12-30-10-14
2TLA020073R0900 AS-I ADRESS CABLE
1SBL103001R8132 ASL09-30-32-81
1SBL177001R1101 AF16-30-01-11
1SBL177001R1201 AF16-30-01-12
1SBL177001R1301 AF16-30-01-13
1SBL177001R1401 AF16-30-01-14
1SBL177001R1110 AF16-30-10-11
1SBL177001R1210 AF16-30-10-12
1SBL177001R1310 AF16-30-10-13
1SBL177001R1410 AF16-30-10-14
1SBL157001R1122 AF12-30-22-11
1SBL157001R1222 AF12-30-22-12
1SBL157001R1322 AF12-30-22-13
1SBL157001R1422 AF12-30-22-14